Notices
Computer & Technology Related Post here for help and discussion of computing and related technology. Internet, TVs, phones, consoles, computers, tablets and any other gadgets.

Compaq/HP Dual Input PDU PN?

Thread Tools
 
Search this Thread
 
Old 20 January 2004, 06:07 PM
  #1  
David_Wallis
Scooby Regular
Thread Starter
 
David_Wallis's Avatar
 
Join Date: Nov 2001
Location: Leeds - It was 562.4bhp@28psi on Optimax, How much closer to 600 with race fuel and a bigger turbo?
Posts: 15,239
Likes: 0
Received 1 Like on 1 Post
Post

Anybody got the part number for the dual input PDU? (circa 16 IEC C14iirc outlets)

either that or a proper list of the PDU's availaible as HP's site is poo..

Im sure you can buy three phase PDU's

David

Old 20 January 2004, 07:23 PM
  #2  
ChrisB
Moderator
 
ChrisB's Avatar
 
Join Date: Dec 1998
Location: Staffs
Posts: 23,573
Likes: 0
Received 0 Likes on 0 Posts
Post

I've previously pulled spec's and stuff via ftp.compaq.com.

/pub/products/servers/proliantstorage/power-protection is the folder - loads of PDFs

HTH.

Chris.
Old 20 January 2004, 09:46 PM
  #3  
David_Wallis
Scooby Regular
Thread Starter
 
David_Wallis's Avatar
 
Join Date: Nov 2001
Location: Leeds - It was 562.4bhp@28psi on Optimax, How much closer to 600 with race fuel and a bigger turbo?
Posts: 15,239
Likes: 0
Received 1 Like on 1 Post
Post

Cheers Chris..

ftp://ftp.compaq.com/pub/products/servers/proliantstorage/power-protection/dualpdu-datasheet.pdf

191186-B31

Somehow suspect this is discontinued as it uses 12 C13 outlets and these have been replaced with the new modular pdu's..

Background is..

4 Cabinet's 1 or two pdu's per cabinet..

Server with redundant PSU's... not really planned when installed. (not me) so both PSU's plugged into same pdu same phase..

One PSU in a machine failed... the Main Breaker tripped in the distribution board.. Thus cutting 20Amps worth of power...

Thats around 10 servers..

Im just building a 10000 series rack.. with G3 DL380's

Only has 4 at the moment, however it has two modular pdu's one on the Red Phase.. and awaiting confirmation from HP / Compaq then the other will be supplied from a different cable / breaker / phase... possibly even a different 40kva Ups..

It will be stictly enfored that all servers must be cabled by this std..

If we cant go across phases then dual input.. but dual input will be better for servers with only one PSU, IE Proliant 1600R's and DL360's

David
Related Topics
Thread
Thread Starter
Forum
Replies
Last Post
JimBowen
ICE
5
02 July 2023 01:54 PM
scoobhunter722
ScoobyNet General
52
20 October 2015 04:32 PM
Nick_Cat
Computer & Technology Related
2
26 September 2015 08:00 AM
turbotog
Wheels, Tyres & Brakes
11
24 September 2015 08:07 PM
Bazil_SW
Engine Management and ECU Remapping
24
21 September 2015 11:55 PM



Quick Reply: Compaq/HP Dual Input PDU PN?



All times are GMT +1. The time now is 02:16 AM.