Central heating & hot water

Old Aug 7, 2013 | 09:16 PM
  #1  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default Central heating & hot water

Ok, I'm hoping someone can shed some light on this.

The central heating in my house has been off for some time with the weather, and I have a power shower, so no need to heat the water either.

So the other day, I decided on a soak in the bath, put the hot water on, and lo and behold, all the upstairs radiators came on full blast! It was like a furnace!

Any ideas before I ring a central heating engineer? (Need a plumber anyway as one of the downstairs radiators leaks when it's on)

Better still, any central heating engineers on here in the east mids want to come take a look? Lol
Reply
Old Aug 7, 2013 | 09:18 PM
  #2  
scoobynutta555's Avatar
scoobynutta555
Scooby Regular
 
Joined: Feb 2001
Posts: 8,541
Likes: 0
From: Markyate.Imprezas owned:-wrx-sti5typeR-p1-uk22b-modded my00. Amongst others!
Default

My ch used to come on with only the hot water selected on the control panel. A motorised valve was faulty. More than likely something similar has happened to you, the valve has stopped in an open position or something.
Reply
Old Aug 7, 2013 | 09:25 PM
  #3  
dpb's Avatar
dpb
Scooby Regular
 
Joined: Nov 2003
Posts: 46,493
Likes: 13
From: riding the crest of a wave ...
Default

Do you own an adjustable?
Reply
Old Aug 7, 2013 | 09:28 PM
  #4  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by scoobynutta555
My ch used to come on with only the hot water selected on the control panel. A motorised valve was faulty. More than likely something similar has happened to you, the valve has stopped in an open position or something.
Hmmm... Ok. Might be worth a look, but I really don't have a Scooby (pun intended) about central heating! Lol.

Originally Posted by dpb
Do you own an adjustable?
I own at least half a dozen! Lol
Reply
Old Aug 7, 2013 | 09:31 PM
  #5  
scoobynutta555's Avatar
scoobynutta555
Scooby Regular
 
Joined: Feb 2001
Posts: 8,541
Likes: 0
From: Markyate.Imprezas owned:-wrx-sti5typeR-p1-uk22b-modded my00. Amongst others!
Default

Neither do I google your symptoms. I have a British Gas service contract and they fixed it. I told them what I thought it was after googling, they confirmed and changed the part, all is fine now
Reply
Old Aug 7, 2013 | 09:32 PM
  #6  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by scoobynutta555
Neither do I google your symptoms. I have a British Gas service contract and they fixed it. I told them what I thought it was after googling, they confirmed and changed the part, all is fine now
Nice one, thanks. I'll have a look.

I do have a plumber who's good, it's just getting hold of him! Lol
Reply
Old Aug 7, 2013 | 09:37 PM
  #7  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

A clue as to your system type would help loads...eg..combi...back boiler ..unvented etc
Reply
Old Aug 7, 2013 | 09:49 PM
  #8  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog
A clue as to your system type would help loads...eg..combi...back boiler ..unvented etc
It's a standard boiler and immersion tank setup with a water tank in the loft. That's about as much as I can tell you really...

I can strip and rebuild a car, computer, or electronics, but heating? Nope, not a clue. Lol
Reply
Old Aug 7, 2013 | 09:53 PM
  #9  
scoobynutta555's Avatar
scoobynutta555
Scooby Regular
 
Joined: Feb 2001
Posts: 8,541
Likes: 0
From: Markyate.Imprezas owned:-wrx-sti5typeR-p1-uk22b-modded my00. Amongst others!
Default

Same set up as me. I'm crap with cars though but run multi million pound machinery at work
Reply
Old Aug 7, 2013 | 09:59 PM
  #10  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by scoobynutta555
Same set up as me. I'm crap with cars though but run multi million pound machinery at work
Lol. Well I work in IT (server side) for an engineering firm, and have rebuilt cars and engines for years. I can take off/replace a radiator ok, and drain and bleed a system, and i'm happy doing "cold" plumbing but when it comes to the gas/boiler/pump side of things, it's a big no for me! Lol.
Reply
Old Aug 7, 2013 | 10:04 PM
  #11  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

post a pic of your airing cupboard pipework
Reply
Old Aug 7, 2013 | 10:10 PM
  #12  
Chip's Avatar
Chip
Scooby Regular
 
Joined: Feb 1999
Posts: 11,758
Likes: 0
From: Cardiff. Wales
Default

Motorised valve by sound of it
Reply
Old Aug 7, 2013 | 10:12 PM
  #13  
scoobeenut's Avatar
scoobeenut
Scooby Regular
 
Joined: Apr 2007
Posts: 581
Likes: 0
From: west London
Default

Motorized valve stuck in mid position, hit it with a hammer to free it up then order a new part before winter comes.
Reply
Old Aug 7, 2013 | 10:14 PM
  #14  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog
post a pic of your airing cupboard pipework
Just above the immersion (that's right isn't it?) is an open water tank, and another covered one in the loft.

There's three pipes from the boiler, a heating "isolator" and the last unmarked switch is apparently the immersion switch.
Attached Thumbnails Click image for larger version

Name:	image-2795570262.jpg
Views:	0
Size:	49.7 KB
ID:	13122   Click image for larger version

Name:	image-2121825196.jpg
Views:	0
Size:	44.6 KB
ID:	13123   Click image for larger version

Name:	image-3711754898.jpg
Views:	0
Size:	47.9 KB
ID:	13124   Click image for larger version

Name:	image-1639599622.jpg
Views:	0
Size:	41.2 KB
ID:	13125   Click image for larger version

Name:	image-1007597872.jpg
Views:	0
Size:	32.3 KB
ID:	13126  

Click image for larger version

Name:	image-1816067597.jpg
Views:	0
Size:	35.9 KB
ID:	13127   Click image for larger version

Name:	image-710705765.jpg
Views:	0
Size:	32.5 KB
ID:	13128  
Reply
Old Aug 7, 2013 | 10:18 PM
  #15  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

You have a 3 way valve,turn on heating and water seperately and note wether the marker on the valve moves to the selected points,it has 3 positions,hot water,heating and both.
Reply
Old Aug 7, 2013 | 10:19 PM
  #16  
AndyC_772's Avatar
AndyC_772
Scooby Regular
iTrader: (2)
 
Joined: Mar 2001
Posts: 9,096
Likes: 0
From: Swilling coffee at my lab bench
Default

As above, your motorised valve has seized. It happens a lot.

You might be able to take the motor off and free up the valve itself by turning it with pliers. Once it's unstuck it might be perfectly OK again, provided the motor hasn't burned out.
Reply
Old Aug 7, 2013 | 10:21 PM
  #17  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog
You have a 3 way valve,turn on heating and water seperately and note wether the marker on the valve moves to the selected points,it has 3 positions,hot water,heating and both.
That's the "white box" on the pipe yeah? The one with the black switch in the middle?

It's also got a black switch on the side too...

So if it stays in the middle that's both, water is one side and heating t'other...

If it doesn't move, it's a new part job, or a gentle tap yeah?

Thanks for this BTW!!
Reply
Old Aug 7, 2013 | 10:22 PM
  #18  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by AndyC_772
As above, your motorised valve has seized. It happens a lot.

You might be able to take the motor off and free up the valve itself by turning it with pliers. Once it's unstuck it might be perfectly OK again, provided the motor hasn't burned out.
Ok, thanks bud. I'll take a look and see if it can be opened.

Reply
Old Aug 7, 2013 | 10:26 PM
  #19  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

Originally Posted by Frenchwood
That's the "white box" on the pipe yeah? The one with the black switch in the middle?

It's also got a black switch on the side too...

So if it stays in the middle that's both, water is one side and heating t'other...

If it doesn't move, it's a new part job, or a gentle tap yeah?

Thanks for this BTW!!
Yes the other black slider is a manual opener..if the valve doesnt move when heat is called for try releasing it with the manual opener....its odd if you havent used the heating for a while that its stuck in mid position,it defaults to hot water,inside theres a motor called a synchron...its an easy diy mend,but do the tests 1st.

Last edited by Busterbulldog; Aug 7, 2013 at 10:27 PM.
Reply
Old Aug 7, 2013 | 10:30 PM
  #20  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Assuming this actuator is at fault, How difficult are these to change? (On a Haynes Spanner scale) lol.

Is it a DIY job? Empty the system, change the part, refill with inhibitor and bleed?

Or should I just call an engineer? If so, how much are we talking?

Ta!!
Reply
Old Aug 7, 2013 | 10:32 PM
  #21  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog

Yes the other black slider is a manual opener..if the valve doesnt move when heat is called for try releasing it with the manual opener....its odd if you havent used the heating for a while that its stuck in mid position,it defaults to hot water,inside theres a motor called a synchron...its an easy diy mend,but do the tests 1st.
Ok, that's cool. I've got the water on and given it a good rap with my knuckles. It went "clunk" inside... And the radiators don't seem to be getting warm.
Reply
Old Aug 7, 2013 | 10:36 PM
  #22  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Radiators are definitely staying cool.

I'm happy with that!

Next job is to freeze the pipes before a valve on a radiator, and replace the leaky valve!

Not looking forward to that as I've just laid a new carpet in that room! Pfft.

I'll check on the actuator again tomorrow and see if its still playing ball!

Thanks for the help folks, much appreciated!
Reply
Old Aug 7, 2013 | 10:37 PM
  #23  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

happy days..put some fernox in your heating tank
Reply
Old Aug 7, 2013 | 10:38 PM
  #24  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

Originally Posted by Frenchwood
Radiators are definitely staying cool.

I'm happy with that!

Next job is to freeze the pipes before a valve on a radiator, and replace the leaky valve!

Not looking forward to that as I've just laid a new carpet in that room! Pfft.

I'll check on the actuator again tomorrow and see if its still playing ball!

Thanks for the help folks, much appreciated!
post a pic of leaky valve there maybe a quick fix
Reply
Old Aug 7, 2013 | 10:46 PM
  #25  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog
happy days..put some fernox in your heating tank
Fernox? Whassat? Lol.


It's leaking from the bottom of the compression joint on the valve I've tightened it to a surreal level, and when the valve is on it still drips, turn it off, and it stops!

Does it on both sides, I put it down to the fact the radiator isn't mounted properly.
Attached Thumbnails Click image for larger version

Name:	image-4036527466.jpg
Views:	0
Size:	46.6 KB
ID:	13129   Click image for larger version

Name:	image-2113647668.jpg
Views:	0
Size:	38.0 KB
ID:	13130  
Reply
Old Aug 7, 2013 | 10:50 PM
  #26  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

The clue is in the it doesnt leak when turned off....your leak is under the white cap...remove it...tighten the packing gland underneath...hey presto leak gone
Reply
Old Aug 7, 2013 | 10:55 PM
  #27  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog
The clue is in the it doesnt leak when turned off....your leak is under the white cap...remove it...tighten the packing gland underneath...hey presto leak gone
Ok, I'll give that a go. Both sides?

It seemed to slow when I tightened the compression joints, the stopped as I turned them off, I just assumed it was the joint... Lol.

See, better eyes see more clearly!

I'd take you for a pint if you were close! Maybe you should send me your PayPal addy in PM pal, I'll send you a tenner to buy you some beer for your help!! Lol
Reply
Old Aug 7, 2013 | 10:58 PM
  #28  
Busterbulldog's Avatar
Busterbulldog
Scooby Regular
iTrader: (1)
 
Joined: Jun 2012
Posts: 1,247
Likes: 0
From: In my garage
Default

the packing glands tend to trickle un noticed...one thing plumbings taught me is keep going upwards until your sure its dry
Reply
Old Aug 7, 2013 | 11:05 PM
  #29  
Frenchwood's Avatar
Frenchwood
Thread Starter
Scooby Regular
 
Joined: Mar 2013
Posts: 361
Likes: 0
From: Nottingham
Default

Originally Posted by Busterbulldog
the packing glands tend to trickle un noticed...one thing plumbings taught me is keep going upwards until your sure its dry
Okey doke, I'll check it in the morning.

Thanks again matey, I really do owe you some beers!! Lol
Reply
Old Aug 8, 2013 | 09:02 AM
  #30  
Graz's Avatar
Graz
Scooby Regular
 
Joined: Jan 2003
Posts: 3,190
Likes: 0
From: 535D M-Sport Touring
Default

Originally Posted by Frenchwood
Next job is to freeze the pipes before a valve on a radiator, and replace the leaky valve!

Not looking forward to that as I've just laid a new carpet in that room! Pfft.
Sound like you're sorted anyway. I wouldn't recommend pipe freezing for the DIY plumber, it only gives you a limited amount of time to sort what ever needs sorting. Far easier to just drain the system down and then you can take as long as you need, which will inevitably be longer than you think as something won't go to plan
Reply