Quick question for the electrical eng's out there!
#1
Quick question for the electrical eng's out there!
Can you help with this, I need to specify to a landlord the power req's for an industrial unit.
Overall there is approx 30 kw req for lighting / ventilation in the storage area of the unit and then the electrical load for a office area (approx 200m2, 50 sockets, electric convection heaters, lights, internal ventilation fans, etc)
I need to convert this load to a KVA power requirement, the supply is 3 phase.
Do you need any more info?
Can anyone do a quick calc, I have had some conflicting advice so far hence the question here!
Thanks
Barrie
Overall there is approx 30 kw req for lighting / ventilation in the storage area of the unit and then the electrical load for a office area (approx 200m2, 50 sockets, electric convection heaters, lights, internal ventilation fans, etc)
I need to convert this load to a KVA power requirement, the supply is 3 phase.
Do you need any more info?
Can anyone do a quick calc, I have had some conflicting advice so far hence the question here!
Thanks
Barrie
#2
Scooby Regular
Join Date: Sep 2000
Location: Notts, UK
Posts: 4,935
Likes: 0
Received 0 Likes
on
0 Posts
If you haven't got any power factor information which you won't have for domestic equipment the nearest you are going to get is a direct KW to KVA conversion.
ie 1KW = 1KVA.
Some of your equipment is going to be single phase such as lighting, computers etc. Is your storage area equipment 3 phase?
Is your landlord asking for load per phase or total load? You can use discrimination to a certain extent ie- you will not have everything on at once but ensure you have enough maximum demand capacity. You may have an electricity contract where you are charged extra for going over you maximum demand so check the small print.
Lee
edited to add..
Not 100% sure what is required for domestic/small industrial 240v 3 phase supplies. Our little unit runs oun nine 4000KVA supplies at 11000V Most of the load is inductive so Power Factor is a big issue.
ie 1KW = 1KVA.
Some of your equipment is going to be single phase such as lighting, computers etc. Is your storage area equipment 3 phase?
Is your landlord asking for load per phase or total load? You can use discrimination to a certain extent ie- you will not have everything on at once but ensure you have enough maximum demand capacity. You may have an electricity contract where you are charged extra for going over you maximum demand so check the small print.
Lee
edited to add..
Not 100% sure what is required for domestic/small industrial 240v 3 phase supplies. Our little unit runs oun nine 4000KVA supplies at 11000V Most of the load is inductive so Power Factor is a big issue.
Last edited by logiclee; 28 June 2004 at 02:13 PM.
#4
A lot of that gear looks like it is going to be mostly resistive so as Lee says a direct conversion might get pretty close. It doesn't look like there is a lot of highly inductive gear in there, nearly impossible to tell though.
I'm no good at this power stuff anyhow but do the supply companies not like you to put in big caps if you are running lots of very inductive gear?
I'm no good at this power stuff anyhow but do the supply companies not like you to put in big caps if you are running lots of very inductive gear?
#5
They love you for putting it big caps!! They call it local pf correction. It saves the grid havign to supply loads of reactive power (kVAr).........which they dont like doing, as it drops the system voltage.
#6
Scooby Regular
Join Date: Sep 2000
Location: Notts, UK
Posts: 4,935
Likes: 0
Received 0 Likes
on
0 Posts
Originally Posted by hedgehog
I'm no good at this power stuff anyhow but do the supply companies not like you to put in big caps if you are running lots of very inductive gear?
As a by product we produce Methane as waste, we've just installed two 2.4MegaWatt generators that burn the methane and that also helps with the Leccy bill, The V20 Turbo engines look beasts as well.
Leccy bill can still run at £1million a quarter though.
Lee
#7
Just re-read the question..............provide more info (why, etc) and you are bound to get an answer.......!
30kW is bugger all really, so if u r looking to buy some plant, just over rate it a little!!!
The only time when kW does not almost = kVA is when you have induciton motors running fans, machinery etc, so i would be inclined not to worry about the pf.
Make sure you get the 3 phase kVA correct though. You may need to get a 1.41 (root 2) in there somewhere, so be careful!!
Cheers,
Matt.
30kW is bugger all really, so if u r looking to buy some plant, just over rate it a little!!!
The only time when kW does not almost = kVA is when you have induciton motors running fans, machinery etc, so i would be inclined not to worry about the pf.
Make sure you get the 3 phase kVA correct though. You may need to get a 1.41 (root 2) in there somewhere, so be careful!!
Cheers,
Matt.
Trending Topics
#8
Hmmm, that will be why I did chemical eng and not electrical stuff then, and here was me thinking that all I had to do was plug it in and it would work
Have been advised that 35 kva per phase should provide plenty of power.
Anyone care to disagree?
Thanks
Have been advised that 35 kva per phase should provide plenty of power.
Anyone care to disagree?
Thanks
#9
Scooby Regular
Join Date: Nov 2001
Location: Leeds - It was 562.4bhp@28psi on Optimax, How much closer to 600 with race fuel and a bigger turbo?
Posts: 15,239
Likes: 0
Received 1 Like
on
1 Post
Have been advised that 35 kva per phase should provide plenty of power.
Anyone care to disagree?
Anyone care to disagree?
#10
u could be over-rated by 3......! But who cares, it aint your cash!!
If you install an overrated transformer, you need to up rate the bus as it will have more short circuit capacity.........!
If you install an overrated transformer, you need to up rate the bus as it will have more short circuit capacity.........!
#11
Scooby Regular
Join Date: Sep 2000
Location: Notts, UK
Posts: 4,935
Likes: 0
Received 0 Likes
on
0 Posts
Originally Posted by Barrie
Have been advised that 35 kva per phase should provide plenty of power.
Anyone care to disagree?
Thanks
Some big Photocopiers can require their own 5KW supply so be carefull if you are going to need one.
Ensure you get the pro's in to install the correct dis-board and protection systems. You will need to do a plan of what equipment you are having and where it is going to be sited.
Cheers
Lee
Thread
Thread Starter
Forum
Replies
Last Post
Brzoza
Engine Management and ECU Remapping
1
02 October 2015 05:26 PM