Any electricians out there? need some help

Old Aug 24, 2015 | 08:32 AM
  #1  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default Any electricians out there? need some help

Fuse for the down stairs plugs popped during the night.

Assumed something has died and unplugged everything (literally out the wall) turned it back on and pop it goes again ..

Help? I have no idea what else to do now?
Reply
Old Aug 24, 2015 | 08:37 AM
  #2  
JDM_Stig's Avatar
JDM_Stig
Scooby Regular
15 Year Member
Liked
Loved
iTrader: (3)
 
Joined: Feb 2009
Posts: 5,873
Likes: 44
From: Mount Weather
Default

When u say unplugged do you have any switched or unwatched spurs for say a extract fan ?
Reply
Old Aug 24, 2015 | 08:45 AM
  #3  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default

Every single plug attached to that circuit is unplugged and the switch off. It's my downstairs all upstairs plugs have been tested and are working, no faulty devices, on the off chance it's been wired wrong.

If the power was staying on, no device would have power, the cooker has it's own circuit and is working fine, but is also off.
Reply
Old Aug 24, 2015 | 08:46 AM
  #4  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default

oh and I have no outdoor lights.
Reply
Old Aug 24, 2015 | 08:58 AM
  #5  
hodgy0_2's Avatar
hodgy0_2
Scooby Regular
15 Year Member
Liked
Loved
Community Favorite
 
Joined: Jul 2008
Posts: 15,634
Likes: 22
From: K
Default

I had a similar problem,

Fuse blowing but no devices attached (as far as I could tell)

So I had to do some thinking and proper PD-ing

It looked like it was a junction box - and when I opened it a gooey mess came out

A spider had obviously crawled in and inadvertently made a connection between the live and neutral - for a short time the we spider had become part of the national grid

Cleaned out the goo (which was still making a connection) and all good

Last edited by hodgy0_2; Aug 24, 2015 at 08:59 AM.
Reply
Old Aug 24, 2015 | 09:21 AM
  #6  
kevo10's Avatar
kevo10
Scooby Regular
 
Joined: Oct 2010
Posts: 1,094
Likes: 0
From: Kings Norton, birmingham
Default

Im no sparky .but from experience at work (in a school) the mcb do tend to not be up to yje job after a few years service. I make it a general rule that if it trips twice , theres either a faulty mcb or there is a prblem other than old age. We have had them go bad after just 3 or 4 years in use
Reply
Old Aug 24, 2015 | 10:04 AM
  #7  
JDM_Stig's Avatar
JDM_Stig
Scooby Regular
15 Year Member
Liked
Loved
iTrader: (3)
 
Joined: Feb 2009
Posts: 5,873
Likes: 44
From: Mount Weather
Default

call a sparks or find a insulation resistance tester to test the cables if you are 100% sure there is nothing left connected on the ring main,
or just swap the cables from 1 ring main to the mcb for another to test that,
if they are on the same side of the board then it`s just a case of swapping the lives from mcb one to another.

hth
Reply
Old Aug 24, 2015 | 10:23 AM
  #8  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default

I've reached my level of electrical risk looking for a sparky now
Reply
Old Aug 24, 2015 | 10:23 AM
  #9  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Default

Is it a rewireable fuse a mcb or an rcd that is tripping.Just noticed you have no outside lights so i would go for these first as possibly being the problem.

Last edited by johned; Aug 24, 2015 at 10:28 AM. Reason: extra info.
Reply
Old Aug 24, 2015 | 10:40 AM
  #10  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default

It was a loose earth in a plug socket .. I took my sockets off and found it.. seems ok now.
Reply
Old Aug 24, 2015 | 10:54 AM
  #11  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Default

Great stuff.
Reply
Old Aug 24, 2015 | 01:25 PM
  #12  
legb4rsk's Avatar
legb4rsk
Scooby Regular
 
Joined: Oct 2004
Posts: 2,684
Likes: 0
From: If you're not braking or accelerating you're wasting time.
Default

Originally Posted by pimmo2000
It was a loose earth in a plug socket .. I took my sockets off and found it.. seems ok now.

Has your other half recently increased your life insurance?








Reply
Old Aug 24, 2015 | 02:23 PM
  #13  
JDM_Stig's Avatar
JDM_Stig
Scooby Regular
15 Year Member
Liked
Loved
iTrader: (3)
 
Joined: Feb 2009
Posts: 5,873
Likes: 44
From: Mount Weather
Default

A loose earth wouldnt cause overload protection to kick in . . either MCB or fuse
Reply
Old Aug 24, 2015 | 05:27 PM
  #14  
andy97's Avatar
andy97
Scooby Regular
iTrader: (1)
 
Joined: Aug 2004
Posts: 6,296
Likes: 118
From: Api 500+bhp MD321T @91dB Probably SN's longest owner of an Impreza Turbo
Default

Wiring is pretty straight forward to diagnose, if you have a decent multi meter.
most of it can be done from fuse/consumer board

Identify is it wiring or appliance fault, I am assuming wiring fault

Turn off main switch to fuse board.

Identify then isolate the faulty circuit, (remove live wires from circuit breaker.)

Measure first short/leakage between live and neutral, there should be no leakage or short.

Measure between the two Brown wires for continuity on ring circuit, there should be.

measure for continuity between earth and neutral, there should be

finally measure continuity of neutral wires by disconnecting these from circuit.

The difficult/boring bit is then going around checking each point to find problem.
Reply
Old Aug 25, 2015 | 07:59 AM
  #15  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default

Originally Posted by JDM_Stig
A loose earth wouldnt cause overload protection to kick in . . either MCB or fuse
You're right it's gone again
Reply
Old Aug 25, 2015 | 09:01 AM
  #16  
JDM_Stig's Avatar
JDM_Stig
Scooby Regular
15 Year Member
Liked
Loved
iTrader: (3)
 
Joined: Feb 2009
Posts: 5,873
Likes: 44
From: Mount Weather
Default

has anything been replaced electrical recently ?
Have you done any work on the house recently electrical or not ?
Reply
Old Aug 25, 2015 | 09:31 AM
  #17  
JGlanzaV's Avatar
JGlanzaV
Scooby Regular
iTrader: (3)
 
Joined: May 2009
Posts: 5,021
Likes: 1
Default

Originally Posted by JDM_Stig
has anything been replaced electrical recently ?
Have you done any work on the house recently electrical or not ?
As above, usually leads you to the problem!

If the outside lights are fed on the same circuit as the ring I'd say without seeing it they probably shouldn't be unless fused down etc, and not a spur off a spur??! And judging by the weather is where I would be looking first off at the outside lights forwater ingress.

Don't try fault finding with a multimeter it won't get you anywhere....

If you have unplugged and isolated/switched off all equipment and it still trips it is a wiring/accesory fault, is it a fuse, mcb or rcd going? It will make a difference as they all trip for different reasons, is it a main rcd or individual rcds?

No need to start taking anything apart just yet until we get to the bottom ofyour set up. Pm me your number and I'll call to talk you through it
Reply
Old Aug 25, 2015 | 11:59 AM
  #18  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Default

Check the outside lights they may have water in them.
Reply
Old Aug 25, 2015 | 12:09 PM
  #19  
Ooperbum's Avatar
Ooperbum
BANNED
 
Joined: Mar 2015
Posts: 176
Likes: 0
From: ooperbum
Default

I wish people would learn to read posts before jumping in with crap. He has said he doesn't have outdoor lights!!!
Reply
Old Aug 25, 2015 | 12:25 PM
  #20  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Smile

Originally Posted by Ooperbum
I wish people would learn to read posts before jumping in with crap. He has said he doesn't have outdoor lights!!!
I apologise for my error but when it was said that there were no outside lights i took it that he meant that they were not working either and as for jumping in with crap i am a fully qualified electrician.
Reply
Old Aug 25, 2015 | 12:52 PM
  #21  
JGlanzaV's Avatar
JGlanzaV
Scooby Regular
iTrader: (3)
 
Joined: May 2009
Posts: 5,021
Likes: 1
Default

Originally Posted by johned
I apologise for my error but when it was said that there were no outside lights i took it that he meant that they were not working either and as for jumping in with crap i am a fully qualified electrician.
I also misread the outside lights. So I wouldn't worry.

Until the OP clarifies his set up its irrelevant all the advice anyways!

I would also suggest that non intrusive fault finding is advised as. The OP has already suggested his electrical knowledge isn't 100% s
Reply
Old Aug 25, 2015 | 12:55 PM
  #22  
JDM_Stig's Avatar
JDM_Stig
Scooby Regular
15 Year Member
Liked
Loved
iTrader: (3)
 
Joined: Feb 2009
Posts: 5,873
Likes: 44
From: Mount Weather
Default

Originally Posted by JGlanzaV
I also misread the outside lights. So I wouldn't worry.

Until the OP clarifies his set up its irrelevant all the advice anyways!

I would also suggest that non intrusive fault finding is advised as. The OP has already suggested his electrical knowledge isn't 100% s
electric shocks are good for the heart muscles, man up
Reply
Old Aug 25, 2015 | 05:42 PM
  #23  
mart360's Avatar
mart360
Scooby Regular
 
Joined: Jul 2005
Posts: 12,329
Likes: 0
Default

Originally Posted by johned
Check the outside lights they may have water in them.
Exactly what i was thinking about 6 posts earlier


Mart
Reply
Old Aug 25, 2015 | 07:36 PM
  #24  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Smile

Originally Posted by JGlanzaV
I also misread the outside lights. So I wouldn't worry.

Until the OP clarifies his set up its irrelevant all the advice anyways!

I would also suggest that non intrusive fault finding is advised as. The OP has already suggested his electrical knowledge isn't 100% s
Thanks and maybe Ooperbum is aptly named.
Reply
Old Aug 25, 2015 | 09:01 PM
  #25  
Ooperbum's Avatar
Ooperbum
BANNED
 
Joined: Mar 2015
Posts: 176
Likes: 0
From: ooperbum
Default

Originally Posted by johned
Ooperbum is aptly named.
Only for you mum!!













Reply
Old Aug 25, 2015 | 09:03 PM
  #26  
Ooperbum's Avatar
Ooperbum
BANNED
 
Joined: Mar 2015
Posts: 176
Likes: 0
From: ooperbum
Default

Originally Posted by johned
as for jumping in with crap i am a fully qualified electrician.
One that can't read good!!







Reply
Old Aug 25, 2015 | 10:12 PM
  #27  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Default

All good.
Reply
Old Aug 27, 2015 | 12:22 PM
  #28  
johned's Avatar
johned
Scooby Regular
15 Year Member
 
Joined: Jan 2010
Posts: 2,002
Likes: 16
From: derbyshire
Default

Did you sort it.
Reply
Old Aug 27, 2015 | 08:47 PM
  #29  
pimmo2000's Avatar
pimmo2000
Thread Starter
Scooby Regular
iTrader: (6)
 
Joined: Sep 2004
Posts: 14,661
Likes: 5
From: On a small Island near France
Default

sort of, he found an issue between kitchen and back room after 3 hours. Needs the kitchen floor taking up, believe there to be a junction box under there.

He has removed said issue by isolating the wire.
Reply
Related Topics
Thread
Thread Starter
Forum
Replies
Last Post
s_tubb23
General Technical
4
Oct 14, 2015 07:58 PM
DogsofWar
Engine Management and ECU Remapping
16
Sep 23, 2015 07:41 PM
alcazar
Non Scooby Related
25
Sep 11, 2015 08:45 PM
wrxmania
Scotland
11
Oct 28, 2013 04:54 PM
keith cowie
Scotland
2
Apr 3, 2004 11:35 PM


Thread Tools
Search this Thread

All times are GMT +1. The time now is 05:43 PM.